Aksa Diesel Generator APD-ULJ300 (300kW)

Share this product!

Aksa Diesel Generator APD-ULJ300 (300kW)

Call for Price

SKU: APD-ULJ300

The AKSA Power Generation APD-ULJ300 is a UL2200-listed, 300 kW diesel standby generator set built around a John Deere 6090HFG86 engine and a Stamford alternator. Engineered for reliable emergency and standby power in commercial and industrial applications, it pairs a DSE 7320 MK II digital control panel with a heavy-duty steel and aluminum enclosure available in open skid, Level 1, or Level 2 sound-attenuated configurations. The unit meets NFPA 70, 99, 110, and 37 Level 1 requirements and is backed by a 24-month / 2,000-hour limited standby warranty. 

Key Features 

  • 300 kW / 375 kVA standby power output at 0.8 power factor, 60 Hz / 1800 rpm 
  • Powered by a John Deere 6090HFG86 diesel engine (9L, 6-cylinder, turbocharged & air-to-air aftercooled), designed to meet EPA Tier 3 
  • Stamford alternator with Class H insulation, IP23 protection, and ±1% voltage regulation 
  • DSE 7320 MK II digital controller — UL & NFPA 110 compatible, with SCADA monitoring and remote display support 
  • UL2200 certified and meets NFPA 70, 99, 110, and 37 Level 1 standards 
  • Available in Open Skid, Level 1, and Level 2 sound-attenuated enclosure configurations 
  • Heavy-duty steel/aluminum enclosure with critical grade silencer and sound-absorbing foam 
  • Engine jacket water heater (Hotstart) and battery charger (ComAp InteliCharger) included as standard 
  • UL142-listed sub-base fuel tank options available in 24-hour, 48-hour, and 72-hour capacities 
  • 24 months / 2,000 hours limited standby warranty, with extended coverage available 
Share:
Descripción
Additional Info
Reviews
Descripción

 

APD-ULJ300 product details and specifications:

General Characteristics 

  • Model Name: APD-ULJ300 
  • Engine Make: John Deere 
  • Engine Model: 6090HFG86 
  • Alternator Make: Stamford 
  • Control Panel Make & Model: DSE 7320 MK II 
  • Frequency & Speed: 60 Hz, 1800 rpm 
  • Enclosure Make & Model: AKSA AUL 71/72 

Genset Rating 

  • Standby Power: 300 kW at 0.8 Power Factor 
  • 480/277V — Alternator HCI434D (Wnd-311) — 452A Standby Current 
  • 240/120V — Alternator S4L1S-E (Wnd-311) — 902A Standby Current 
  • 208/120V — Alternator S4L1S-E (Wnd-311) — 1041A Standby Current 
  • 600/347V — Alternator HCI434D (Wnd-17) — 361A Standby Current 

Engine Data 

  • Manufacturer: John Deere 
  • Model: 6090HFG86 
  • Displacement & Cylinders: 9 L / 6 Cylinders 
  • Engine Type: In-line, 4 Cycle 
  • Engine Speed: 1800 rpm 
  • Engine Standby Power: 345 kW 
  • Aspiration: Turbocharged & Air to Air Aftercooled 
  • Compression Ratio: 16.0 : 1 
  • Bore / Stroke: 4.66 in / 5.35 in (118.4 mm / 136 mm) 
  • Governor Type: Electronic 
  • Engine Crankcase Vent System: Open 
  • Fan Power: 13.8 kW 
  • BMEP, Standby Power: 2556 kPa 
  • Friction Power: 24 kW 
  • Designed / Calibrated to Meet: EPA Tier 3 

Fuel System 

  • ECU Description: L14 Controller 
  • Max Fuel Inlet Temp.: 176 °F 
  • Total Fuel Flow: 450 lb/hr 

Fuel Consumption 

  • Standby Power (100%): 22.11 gal/h 
  • Standby Power (75%): 17.78 gal/h 
  • Standby Power (50%): 13.07 gal/h 
  • Standby Power (25%): 6.92 gal/h 

Electric System 

  • System Voltage: 12V / 24V 
  • Min Voltage at ECU during crank: 6V for 12V system / 10V for 24V system 
  • Battery Qty, Rating: 2 x 120Ah 

Cooling System 

  • Radiator Cooling System Type: Closed Circuit 
  • Radiator Ambient Temp: > 50 °C 
  • Coolant Capacity, Engine Only: 16.9 quart 
  • Max Top Tank Temp: 230 °F 
  • Thermostat, Start – Fully Open: 180–201 °F 

Exhaust System 

  • Exhaust Temperature: 927 °F 
  • Max Allowable Exhaust Restriction: 7.5 kPa 
  • Exhaust Gas Flow: 2246 ft³/min 

Air Intake System 

  • Engine Air Flow: 936 ft³/min 
  • Max Intake Air Restriction (Clean Element): 3.75 kPa 
  • Air Filter Type: Dry Paper Element 

Lubrication System 

  • Oil Pressure at Rated Speed: 260 kPa 
  • In-Pan Oil Temperature: 241 °F 
  • Max Oil Carryover in Blow-by: 0.002 lb/hr 
  • Max Crankcase Pressure: 0.5 kPa 

Alternator Data 

  • Manufacturer: Stamford 
  • Standards: BS EN 60034 
  • Control System: PMG 
  • A.V.R.: MX341 
  • Voltage Regulation: ± 1% 
  • Insulation System: Class H 
  • Protection: IP23 
  • Rated Power Factor: 0.8 
  • Stator Winding: Double Layer Concentric 
  • Winding Pitch: Two Thirds 
  • Winding Leads: 12 
  • Telephone Interference: THF < 2% 
  • Waveform Distortion: No Load < 1.5% 
  • Maximum Over Speed: 2250 rev/min 

Controller Data 

  • Manufacturer: DSE 
  • Model: 7320 MK II 
  • Microprocessor controlled, UL & NFPA110 Compatible 
  • License free PC Software (Non-proprietary Software) 
  • IP65 rating offers increased resistance to water ingress 
  • Modules can be integrated to building management systems 
  • Real time clock provides accurate event log 
  • Four line back-lit LCD text display 
  • Five key menu navigation, two wire start/stop at Auto mode 
  • Front panel editing with PIN protection 
  • Support up to three remote display modules 
  • Configurable timers and alarms 
  • Multiple date and timer scheduler 
  • Integral PLC editor 
  • 'Protections disabled' feature 
  • Load switching (load shedding and dummy load outputs) 
  • Fully configurable via DSE Configuration Suite PC Software 
  • SCADA monitoring via DSE Configuration Suite PC Software 

Battery Charger & Electrical System Data 

  • Manufacturer: ComAp 
  • Model: InteliCharger 
  • Input Voltage: 85V ~ 264V AC 
  • Output Voltage / Current: 27.2V Float / 2.5A pk 

Jacket Water Heater Data 

  • Manufacturer: Hotstart 
  • Model: CTM25210-N00 
  • Input Voltage: 240V 
  • Power: 2500W 

Protection 

  • Gen. Voltage – under / over 
  • Gen. Freq. – under / over 
  • Engine Speed – under / over 
  • Engine Oil Pressure – low 
  • Engine Temp – low / high 
  • Battery Voltage – low / high 
  • Weak Battery 
  • Fail to Start / Stop 
  • Charge Alternator Fail 
  • Over Current & Load (kW/kVAr) 
  • Unbalanced Load 
  • Independent Earth Fault 
  • Reverse Power 
  • Loss of Speed Signal 

Instruments 

  • Gen. Voltage (L-L/L-N) 
  • Gen. Frequency 
  • Engine Speed 
  • Oil Pressure 
  • Water Temperature 
  • Battery Voltage 
  • Run Time 
  • Phase Sequence 
  • Power monitoring (kWh/kVAh/kVArh) 
  • Power (kWh/kVAh/kVArh) 
  • Power Factor 
  • Generator Current 
  • Generator Load (%) 
  • Earth Current 

Enclosure Features 

  • Heavy Duty Steel / Aluminum Structure 
  • E-Stop on Enclosure 
  • Control Panel Eliminated from Engine Vibrations 
  • Standard Sound Attenuation Foam 
  • Plastic Covered Corrosion Resistant Locks & Hinges 
  • Internally Mounted Exhaust System with Rain Cap 
  • Coolant Fill Cap 
  • Removable Base Frame Lifting Hooks 
  • Oil & Coolant Drain Ports 
  • Easy Access for Maintenance 

Dimensions & Weight — Open Skid Gen 

  • Length: 157.5 in 
  • Width w/o lift hooks: 74.8 in 
  • Height: 71 in 
  • Dry Weight: 7325 lb 

Dimensions & Weight — Level 1 Enclosure 

  • Length: 205 in 
  • Width w/o lift hooks: 77 in 
  • Height: 89.9 in 
  • Dry Weight: 10750 lb 
  • Sound Pressure @ 7 meters: 77 dB(A) 

Dimensions & Weight — Level 2 Enclosure 

  • Length: 224.6 in 
  • Width w/o lift hooks: 77 in 
  • Height: 89.9 in 
  • Dry Weight: 11125 lb 
  • Sound Pressure @ 7 meters: 75 dB(A) 

Fuel Tank — UL142 Listed Base Design 

  • 24hr (600 gal): Dimensions (L/W/H) 225 / 74.8 / 14.5 in — Weight 2800 lb 
  • 48hr (1200 gal): Dimensions (L/W/H) 225 / 74.8 / 25.5 in — Weight 3550 lb 
  • 72hr (1780 gal): Dimensions (L/W/H) 225 / 74.8 / 36 in — Weight 4200 lb 

Standard Features & Accessories 

  • UL2200 Certification 
  • Heavy Duty Steel Base Frame 
  • PMG w/MX341 AVR 
  • Engine Jacket Water Heater 
  • Battery and Battery Rack 
  • Battery Charger 
  • Anti Vibration Pads between Engine/Alternator & Base Frame 
  • Critical Grade Silencer Inside Enclosure 
  • Residential Grade Silencer Set for Open Skid Sets 
  • Exhaust outlet rain cap and radiator fill cap 
  • Sound Absorb Foam Material for Enclosure 
  • Emergency Stop Button 
  • Oil Drain Valve 
  • Coolant Drain Valve 
  • Jacket Water Heater Isolation Valves 
  • Flex Fuel Lines 
  • Air Filter Restriction Gauge 
  • Engine Manifold Cover 
  • Turbocharger Cover 
  • Protection Covers for Rotating Parts 
  • Exhaust Insulation Cover 
  • Enclosure DC Light 
  • Operations Manual 
  • 24 Months / 2000 hours Limited Standby Warranty 

Optional Accessories 

  • Main Line CB (3 / 4 Poles – 80% / 100% rated) 
  • Upsize Alternator 
  • Voltage Regulation ±0.5% w/MX321 AVR 
  • Anti-condensation Heater 
  • Sub Base Fuel Tank (UL142 / UL2085) 
  • Fuel Level Display & Alarm on Controller 
  • Low / High Fuel Alarms 
  • Fuel Water Separator Filter 
  • Auto Fuel Fill Control System 
  • Oil Temperature Display on Controller 
  • Manual Speed Adjust Rheostat 
  • Manual Voltage Adjust Rheostat 
  • Remote Annunciator Panel 
  • Remote Control & Monitoring Panel 
  • Advanced SMS Messaging 
  • Control Panel Heater 
  • Battery Disconnect Switch 
  • Battery Heater 
  • Battery Charger 10/20 Amp 
  • Shunt Trip / Aux Contacts 
  • Spring Anti-vibration Isolators 
  • Automatic Transfer Panel (ATS) 
  • 5 Years / 2000 hours Limited Comprehensive Warranty 

Codes & Standards 

  • Designed and manufactured in a facility certified to ISO 9001 standards 
  • Designed and manufactured in a facility certified to ISO 14001:2015 standards 
  • AKSA Power Generation provides single source responsibility for the generator set & accessories 
  • Prototype tested and production tested according to the UL test program 
  • Meets NFPA 70, 99, 110, 37 Level 1 when equipped with necessary accessories and installed per NFPA standards 
  • UL2200 Listed — Diesel 
  • EPA – Certified for Emergency Stationary Applications 

product specifications:

SpecificationValue
Model NameAPD-ULJ300
Engine MakeJohn Deere
Engine Model6090HFG86
Alternator MakeStamford
Control Panel Make & ModelDSE 7320 MK II
Frequency & Speed60 Hz, 1800 rpm
Enclosure Make & ModelAKSA AUL 71/72
Standby Power Rating300 kW
Power Factor0.8
Displacement & Cylinders9 L / 6 Cylinders
Engine TypeIn-line, 4 Cycle
Engine Standby Power345 kW
AspirationTurbocharged & Air to Air Aftercooled
Compression Ratio16.0 : 1
Bore / Stroke4.66 in / 5.35 in
Governor TypeElectronic
Engine Crankcase Vent SystemOpen
Fan Power13.8 kW
BMEP, Standby Power2556 kPa
Friction Power24 kW
Designed / Calibrated to MeetEPA Tier 3
ECU DescriptionL14 Controller
Max Fuel Inlet Temp.176 F
Total Fuel Flow450 lb/hr
Fuel Consumption @ 100% Standby Power22.11 gal/h
Fuel Consumption @ 75% Standby Power17.78 gal/h
Fuel Consumption @ 50% Standby Power13.07 gal/h
Fuel Consumption @ 25% Standby Power6.92 gal/h
System Voltage12V / 24V
Min Voltage at ECU during Crank6V (12V system) / 10V (24V system)
Battery Qty, Rating2 x 120Ah
Radiator Cooling System TypeClosed Circuit
Radiator Ambient Temp> 122 F
Coolant Capacity, Engine Only16.9 quart
Max Top Tank Temp230 F
Thermostat, Start - Fully Open180-201 F
Exhaust Temperature927 F
Max Allowable Exhaust Restriction7.5 kPa
Exhaust Gas Flow2246 ft3/min
Engine Air Flow936 ft3/min
Max Intake Air Restriction (Clean Element)3.75 kPa
Air Filter TypeDry Paper Element
Oil Pressure at Rated Speed260 kPa
In-Pan Oil Temperature241 F
Max Oil Carryover in Blow-by0.002 lb/hr
Max Crankcase Pressure0.5 kPa
Alternator StandardsBS EN 60034
Alternator Control SystemPMG
A.V.R.MX341
Voltage Regulation+/- 1%
Insulation SystemClass H
Alternator ProtectionIP23
Rated Power Factor0.8
Stator WindingDouble Layer Concentric
Winding PitchTwo Thirds
Winding Leads12
Telephone InterferenceTHF < 2%
Waveform DistortionNo Load < 1.5%
Maximum Over Speed2250 rev/min
Controller ManufacturerDSE
Controller Model7320 MK II
Battery Charger ManufacturerComAp
Battery Charger ModelInteliCharger
Battery Charger Input Voltage85V - 264V AC
Battery Charger Output Voltage / Current27.2V Float / 2.5A pk
Jacket Water Heater ManufacturerHotstart
Jacket Water Heater ModelCTM25210-N00
Jacket Water Heater Input Voltage240V
Jacket Water Heater Power2500W
Open Skid Gen - Length157.5 in
Open Skid Gen - Width w/o Lift Hooks74.8 in
Open Skid Gen - Height71 in
Open Skid Gen - Dry Weight7325 lb
Level 1 Enclosure - Length205 in
Level 1 Enclosure - Width w/o Lift Hooks77 in
Level 1 Enclosure - Height89.9 in
Level 1 Enclosure - Dry Weight10750 lb
Level 1 Enclosure - Sound Pressure @ 7m77 dB(A)
Level 2 Enclosure - Length224.6 in
Level 2 Enclosure - Width w/o Lift Hooks77 in
Level 2 Enclosure - Height89.9 in
Level 2 Enclosure - Dry Weight11125 lb
Level 2 Enclosure - Sound Pressure @ 7m75 dB(A)
Fuel Tank 24hr (600gal) - Dimensions (L/W/H)225 / 74.8 / 14.5 in
Fuel Tank 24hr (600gal) - Weight2800 lb
Fuel Tank 48hr (1200gal) - Dimensions (L/W/H)225 / 74.8 / 25.5 in
Fuel Tank 48hr (1200gal) - Weight3550 lb
Fuel Tank 72hr (1780gal) - Dimensions (L/W/H)225 / 74.8 / 36 in
Fuel Tank 72hr (1780gal) - Weight4200 lb

 

product related documents:

APD-ULJ300.pdf

Additional Info
Peso11125 lbs
Dimensiones224.6 × 77 × 89.9 in
Reviews

Valoraciones

No hay valoraciones aún.

Solo los usuarios registrados que hayan comprado este producto pueden hacer una valoración.

Item añadido al carrito View Cart Checkout
Item added to wishlist View Wishlist
Item removed from wishlist