McPherson Controls | 200A 3Pole Automatic Transfer Switch | BTB3P2UD200N4
$1,857.00
The BTB3P2UD200N4 integrates the programmable color screen and the switch mechanism into one single unit:
Molded Case switches with integrated controller save space, installation time and cost.
Electrical and mechanical interlock & safety lock.
Easy to install.
It can operate electrically or manually.
200 AMP Transfer Switch, 3 Pole / 3 Phase, 50 Hz or 60 Hz, Multi-Voltage: 220V – 480V NEMA 3R Weather-Proof Enclosure for Indoor or Outdoor use.
Generator Exerciser, day & time adjustable: once a week, once every 2 weeks, once every 3 weeks, once every 4 weeks, without load or with load.
Optional smartphone communications module.
UL 1008 – E511560
Pictures shown are representative and may not reflect exact model or other specifications.
Usually ships in 3-5 business days if in stock at the factory when placing the order.
McPherson Controls BTB3P2UD200N4
Details and Specifications
- Molded Case Circuit Breaker (MCCB) type
- Electrical and Manual operation, Lug connections.
- Safety lock to avoid injury to personnel during maintenance.
- Color LCD display allows direct input of settings.
- All phase voltage/frequency monitor & protection for Utility & Generator.
- Auxiliary contacts to indicate Utility or Generator MCCB closed.
- Adjustable central “OFF” position timer.
- Adjustable Weekly exercise timer from 1 to 4 weeks.
- Both mechanical and electrical interlock protections.
- Optional communication modules for remote monitoring and control with a Smartphone
Product Specifications:
Specifications | |
Rated Voltage | 240 - 480 VAC |
Rated Insulation Voltage Ui (V) | 690 VAC |
Rated Current | 200 Amp |
Rated Frequency | 50/60 Hz |
Switch Type | Molded Case Circuit Breaker |
Poles | 3 Poles |
Remote Start Output | 7A @ 250 Vac Max. |
Auxiliary Output | 3A @ 250 Vac Max. |
Rated Breaking Capacity IEC 60947-2 Icu / Ics (KA) | |
220V / 240V | 50 / 25 |
380V / 415V | 30 / 15 |
440V | 25 / 13 |
550V | 20 / 10 |
Adjustable Timer Settings: | |
TDNE Time Delay Normal to Emergency | 0 to 250 seconds |
TDES Time Delay Engine Start | 0 to 15 seconds |
TDEN Time Delay Emergency to Normal | 0 to 999 seconds |
TDEC Time Delay Engine Cool-down | 0 to 250 seconds |
TDOF Time Delay in OFF position | 0 to 99 seconds |
Environment | |
Operating Temperature | -20 to +60 °C |
Storage Temperature | -30 to +80 °C |
Relative Humidity | Less than 90% |