BLUE STAR Power Systems 425KW Gaseous Generator | NG425-01
BLUE STAR Power Systems 425KW Gaseous Generator | NG425-01
Ranging from 20 – 1050 kWe.
Covering a wide variety of applications in a multitude of environments.
Including special applications that require gaseous options because of local fuel codes, containment, or customer preferences are available in natural gas, propane, and combined fuel options.
Meeting the most current EPA standards ensures offering the most innovative technical solutions for reducing emissions and providing you with the best unit for your application.
All units are UL 2200 Listed, CSA Certified, & Seismic Certified to IBC 2018.
Pictures shown are representative and may not reflect exact model or other specifications.
Available ex factory. (Call to confirm)
BLUE STAR NG425-01
Details and Specifications
Standard Equipment
Engine
- Radiator Cooled Unit Mounted (50˚C)
- Radiator Duct Flange (OPU Only)
- Blower Fan & Fan Drive
- Starter & Alternator
- Oil Pump & Filter
- Oil Drain Extension w/Valve
- Governor - Electronic Isochronous
- 24V Battery System & Cables
- Air Cleaner (Dry Single Stage)
- Critical Grade Silencer Mounted
- Flexible Fuel Connector
- EPA Certified
Generator
- Brushless Single Bearing
- Automatic Voltage Regulator
- ± 0.50% Voltage Regulation
- 4 Pole, Rotating Field
- 125˚C Standby Temperature Rise
- 100% of Rated Load - One Step
- 5% Maximum Harmonic Content
- NEMA MG 1, IEEE and ANSI Standards Compliance for Temperature Rise
Additional
- Single Source Supplier
- UL 2200 & cUL Listed
- CSA Certified
- Seismic Certified to IBC 2021
- NFPA 110 / CSA C282 Compliant
- Microprocessor Based Digital Control Panel Mounted in NEMA 12 Enclosure
- Base - Structural Steel
- Main Line Circuit Breaker Mounted & Wired
- Battery Charger 24V 5 Amp
- Jacket Water Heater -20˚F 5000W 240V w/Isolation Valves
- Vibration Isolation Mounts (Pad Type)
- 2 Year / 2000 Hour Standby Warranty
- Standard Colors - White / Gray
Product Specifications:
Standby Ratings | |||
Voltage | Phase | Generator Model | Connection |
208V | 3 | HCI534D | 12 LEAD WYE |
240V | 3 | HCI534D | 12 LEAD DELTA |
480V | 3 | S4L1D-G41 | 12 LEAD WYE |
Voltage | kWe Nat (LP) | AMPS Nat (LP) | Temp Rise |
208V | 425 (300) | 1476 (1042) | 125˚C / 40˚C |
240V | 425 (300) | 1280 (903) | 125˚C / 40˚C |
480V | 425 (300) | 640 (452) | 125˚C / 40˚C |
DCP7310 Control Panel
Standard Features
- Digital Metering
- Engine Parameters
- Generator Protection Functions
- Engine Protection
- CAN Bus (J1939) ECU Communications
- Windows-Based Software
- Multilingual Capability
- Remote Communications to DSE2548 Remote Annunciator
- 8 Programmable Contact Inputs
- 10 Contact Outputs
- RS485 Communicator Interface
- Culus Listed, CE Approved
- Event Recording
- IP 65 rating (with supplied gasket) offers increased resistance to water ingress
- NFPA 110 Level 1 Compatible
PRODUCT Related documents:
DCP7310 Controller (full spec)
NFPA 110 compliant NRG Series Battery Chargers
Weight | 10925 lbs |
---|---|
Dimensions | 156 × 86 × 98 in |
Only logged in customers who have purchased this product may leave a review.
Reviews