Blue Star VD230-01 (230kWe)



Blue Star VD230-01 (230kWe)
The Blue Star Power Systems VD230-01 is a 230 kWe diesel-powered emergency stationary standby generator set engineered for commercial and industrial applications. Powered by the Volvo TAD851GE engine and paired with a Stamford brushless alternator, this unit delivers reliable backup power at 60 Hz across multiple voltage configurations, housed in a rugged Level 2 weather-proof powder-coated steel enclosure rated for 200 MPH wind loads and UL 2200 Listed.
- 230 kWe standby power rating at 1800 RPM, 60 Hz
- Volvo TAD851GE 6-cylinder inline turbocharged diesel engine with electronic isochronous governor
- Stamford UCDI274J1 brushless single-bearing alternator with MX321 automatic voltage regulator and PMG excitation
- Available in 1-phase 120/240V or 3-phase 277/480V configurations
- Level 2 weather-proof enclosure with 1.5″ Polydamp Type D acoustical foam, 200 MPH wind rated per IBC 2021
- Blue Star DCP7310 microprocessor-based digital control panel with CAN Bus (J1939) communications
- UL 2200 Listed, EPA Tier 3 certified, NFPA 110 compliant, seismic certified to IBC 2021
- 24-hour 540-gallon UL 142 listed double-wall sub-base fuel tank standard (48-hr and 72-hr options available)
- 350A 3-pole 600V mainline circuit breaker, 24V battery charger, and engine block heater rated to -20°F included standard
- 2-year / 2000-hour limited standby warranty
VD230-01 product details and specifications:
General
- Model: VD230-01
- Power Rating: 230 kWe (Standby)
- Fuel Type: Diesel
- Application: Emergency Stationary Standby
- Frequency: 60 Hz
- Speed: 1800 RPM
- UL 2200 Listed: Yes
- EPA Certification: Tier 3
- NFPA 110: Level 1 and Level 2 Compliant
- CSA C282 Compliant
- Seismic Certified to IBC 2021
- Unit Color: White
Engine
- Manufacturer: Volvo Penta
- Model: TAD851GE
- Type: 4-Cycle, 6-Cylinder Inline, Turbocharged with Charge Air Cooling (CAC)
- Displacement: 470 cu. in. (7.70 L)
- Bore x Stroke: 4.33 in. x 5.31 in.
- Compression Ratio: 17.5:1
- Rated RPM: 1800
- Max Standby HP (with fan): 337 HP (248 kW)
- Governor: Electronic Isochronous
- Cooling: Radiator Cooled, Unit Mounted (55°C Ambient)
- Air Cleaner: Dry Single Stage with Restriction Indicator
- Silencer: Critical Grade Compact CPJ Series, Mounted to Engine
- Battery: 24 Volt System with Rack and Cables
- Flexible Fuel Connector: Included
- Oil Drain Extension: Plumbed to Bulkhead Fitting in Base
Generator / Alternator
- Generator Model (480V, 3-Ph): Stamford UCDI274J1, 12 Lead Wired, High Wye
- Generator Model (240V, 1-Ph): Stamford S4L1D-F41, 12 Lead Double Delta
- Type: Brushless Single Bearing
- Voltage Regulator: Stamford MX321 Automatic Voltage Regulator with PMG Excitation
- Voltage Regulation: ± 1.00%
- Poles: 4 Pole, Rotating Field
- Standby Temperature Rise: 125°C over 40°C Ambient
- Load Acceptance: 100% of Rated Load in One Step
- Harmonic Content: 5% Maximum
- Standards: NEMA MG1, IEEE, and ANSI Compliance
- Insulation Class: Class H
- Winding Pitch: 2/3
- Winding Leads: 12
Voltage and Phase Options
- 1-Phase: 120/240V, 60 Hz, 1.0 PF — 958 Amps (Generator Model: S4L1D-F41, 12 Lead DD)
- 3-Phase: 208V, 60 Hz, 0.8 PF — 799 Amps (Generator Model: UCDI274K1, 12 Lead Wye)
- 3-Phase: 240V, 60 Hz, 0.8 PF — 692 Amps (Generator Model: UCDI274K1, 12 Lead Delta)
- 3-Phase: 480/277V, 60 Hz, 0.8 PF — 346 Amps (Generator Model: UCDI274J1, 12 Lead Wye)
- 3-Phase: 600V, 60 Hz, 0.8 PF — 277 Amps (Generator Model: UCDI274J1, 4 Lead Wye)
Control Panel
- Model: Blue Star DCP7310 Microprocessor Based Gen-Set Controller
- Mounting: Facing Left from Generator End (unless specified otherwise)
- Enclosure: NEMA 12
- Display: 4-Line Back-Lit LCD with Five Key Menu Navigation
- Communications: CAN Bus (J1939), RS485, MODBUS RTU and TCP
- Protections: Low Oil Pressure, High Coolant Temp, Overspeed, Overcrank Shutdowns
- Alarms: Emergency Stop Pushbutton, Audible Alarm Buzzer with Silencing Switch
- Inputs: 8 Programmable Contact Inputs
- Outputs: 10 Contact Outputs
- Rating: IP 65 (with supplied gasket)
- NFPA 110 Level 1 Compatible
- cULus Listed, CE Approved
- Event Recording Capability
- Windows-Based PC Software (DSE Configuration Suite)
- Remote Communications: DSE2548 Remote Annunciator Compatible
Enclosure
- Level: Level 2 — Weather Proof with Foam
- Material: Powder Coated 14 Gauge Steel
- Wind Rating: 200 MPH per IBC 2021 and ASCE/SEI 7-16
- Roof: Pitched Roof for Increased Structural Integrity and Improved Watershed
- Intake/Exhaust: Punched Intake with Baffle and Punched Exhaust Openings
- Doors: Keyed Alike Lockable with Draw Down Latches and Stainless Steel Component Hinges
- Sound Attenuation Foam: 1.5" Thick Polydamp Type D Acoustical Foam (PAF)
- Base: Formed Steel with Mounting and Lifting Holes
- Vibration Isolation Mounts Included
Weights and Dimensions
- OPU: 120 in. L x 66 in. W x 72 in. H — 5,125 lbs.
- Level 1 Enclosure: 156 in. L x 66 in. W x 94 in. H — 6,375 lbs.
- Level 2 Enclosure: 156 in. L x 66 in. W x 94 in. H — 6,450 lbs.
- Level 3 Enclosure: 196 in. L x 66 in. W x 94 in. H — 6,750 lbs.
- Note: Allow 6–12 inches additional height for exhaust stack
Sound Data (at 23 ft per ISO 8528-10)
- OPU: 86 dBA No Load / 88 dBA Full Load
- Level 1: 83 dBA No Load / 85 dBA Full Load
- Level 2: 77 dBA No Load / 79 dBA Full Load
- Level 3: 69 dBA No Load / 71 dBA Full Load
Fuel System
- Fuel Consumption at 100% Load: 17.9 gal/hr
- Fuel Consumption at 75% Load: 14.1 gal/hr
- Fuel Consumption at 50% Load: 10.3 gal/hr
- Standard Fuel Tank: 24-Hour / 540 Gallon, UL 142 Listed Sub-Base, Double Wall with Secondary Containment
- Optional Fuel Tank: 48-Hour / 1080 Gallon Sub-Base Fuel Tank
- Optional Fuel Tank: 72-Hour / 1620 Gallon Sub-Base Fuel Tank
- Tank includes: Supply & Return Connections, Fuel Level Gauge, Fuel Leak Switch, Fill & Vent Plumbing
Exhaust, Cooling, and Air Requirements
- Exhaust Gas Temp at Stack: 824°F (440°C)
- Exhaust Gas Volume at Stack: 1,926 CFM
- Max Allowable Exhaust Restriction: 40.0 in. H2O
- Radiator Ambient Capacity: 131°F (55°C)
- Water Pump Flow Rate: 61.8 GPM
- Heat Rejection to Coolant: 6,199 BTU/min (108 kW)
- Aspirating Air: 831 CFM
- Air Flow Required for Radiator Cooled Unit: 13,781 CFM
- Total Oil System: 7.10 gal
- Engine Jacket Water Capacity: 4.49 gal
- System Coolant Capacity: 10.8 gal
Electrical Components
- Mainline Breaker: 350 Amp, 3 Pole, 600 Volt, Mounted and Wired in NEMA 1 Enclosure
- Battery: 24 Volt System with Rack and Cables
- Battery Charger: 24V, 5 Amp (BC2405A Series), Mounted and Wired
- Engine Block Heater: 2500W, 240VAC, Rated for -20°F, Installed with Isolation Valves
Warranty and Testing
- Warranty: 2 Year / 2000 Hour Limited Standby
- Factory Test: Standard Commercial Testing — Verification of Alarm Shutdowns, Voltage Settings, Block Loading to Rated kWe and PF
- All units built and tested to cUL, CSA, and NFPA 110 standards
product specifications:
| Specification | Value |
| Model | VD230-01 |
| Power Rating (Standby) | 230 kWe |
| Fuel Type | Diesel |
| Frequency | 60 Hz |
| Speed | 1800 RPM |
| Application | Emergency Stationary Standby |
| UL 2200 Listed | Yes |
| EPA Rating | Tier 3 |
| NFPA 110 Compliance | Level 1 and Level 2 |
| Seismic Certification | IBC 2021 |
| Engine Manufacturer | Volvo Penta |
| Engine Model | TAD851GE |
| Engine Type | 4-Cycle, 6-Cylinder Inline, Turbocharged with CAC |
| Displacement | 470 cu. in. (7.70 L) |
| Bore x Stroke | 4.33 in. x 5.31 in. |
| Compression Ratio | 17.5:1 |
| Rated RPM | 1800 |
| Max Standby HP (with fan) | 337 HP (248 kW) |
| Governor | Electronic Isochronous |
| Air Cleaner | Dry Single Stage |
| Silencer | Critical Grade Compact (CPJ Series), Mounted to Engine |
| Generator Model (480V, 3-Phase) | Stamford UCDI274J1 |
| Generator Model (240V, 1-Phase) | Stamford S4L1D-F41 |
| Generator Type | Brushless Single Bearing |
| Voltage Regulator | Stamford MX321 AVR with PMG Excitation |
| Voltage Regulation | +/- 1.00% |
| Poles | 4 Pole, Rotating Field |
| Standby Temperature Rise | 125°C over 40°C Ambient |
| Harmonic Content | 5% Maximum |
| Winding Pitch | 2/3 |
| Winding Leads | 12 Lead |
| Insulation Class | Class H |
| Voltage Option 1 (1-Phase) | 120/240V, 1-Phase, 60 Hz, 1.0 PF — 958 A |
| Voltage Option 2 (3-Phase) | 480/277V, 3-Phase, 60 Hz, 0.8 PF — 346 A |
| Control Panel | Blue Star DCP7310 Microprocessor Based Gen-Set Controller |
| Panel Mounting | Mounted Facing Left from Generator End |
| Panel Protection | NEMA 12 Enclosure |
| Cooling System | Unit Mounted Radiator |
| Radiator Ambient Capacity | 131°F (55°C) |
| Water Pump Flow Rate | 61.8 GPM |
| Heat Rejection to Coolant | 6,199 BTU/min (108 kW) |
| Exhaust Gas Temp at Stack | 824°F (440°C) |
| Exhaust Gas Volume at Stack | 1,926 CFM |
| Max Allowable Exhaust Restriction | 40.0 in. H2O |
| Air Aspirating | 831 CFM |
| Air Flow for Radiator Cooled Unit | 13,781 CFM |
| Fuel Consumption at 100% Load | 17.9 gal/hr |
| Fuel Consumption at 75% Load | 14.1 gal/hr |
| Fuel Consumption at 50% Load | 10.3 gal/hr |
| Total Oil System Capacity | 7.10 gal |
| Engine Jacket Water Capacity | 4.49 gal |
| System Coolant Capacity | 10.8 gal |
| Enclosure Level | Level 2 (Weather Proof with Foam) |
| Enclosure Material | Powder Coated 14 Gauge Steel |
| Enclosure Wind Rating | 200 MPH (IBC 2021 / ASCE/SEI 7-16) |
| Sound Attenuation Foam | 1.5" Polydamp Type D Acoustical Foam (PAF) |
| Enclosure Color | White |
| Dimensions L x W x H (Level 2 Enclosure) | 156 x 66 x 94 in. |
| Weight (Level 2 Enclosure) | 6,450 lbs. |
| Dimensions L x W x H (OPU) | 120 x 66 x 72 in. |
| Weight (OPU) | 5,125 lbs. |
| Sound Level No Load (Level 2) | 77 dBA at 23 ft |
| Sound Level Full Load (Level 2) | 79 dBA at 23 ft |
| Mainline Breaker | 350 Amp, 3 Pole, 600 Volt, NEMA 1 Enclosure |
| Battery System | 24 Volt with Rack and Cables |
| Battery Charger | 24V, 5 Amp, Mounted and Wired |
| Engine Block Heater | 2500W, 240VAC, Rated for -20°F, with Isolation Valves |
| Fuel Tank (Standard) | 24-Hour / 540 Gallon, UL 142 Listed Sub-Base, Double Wall |
| Fuel Tank (Optional 48-hr) | 48-Hour / 1080 Gallon |
| Fuel Tank (Optional 72-hr) | 72-Hour / 1620 Gallon |
| Warranty | 2 Year / 2000 Hour Limited Standby |
| Factory Test | Standard Commercial Testing |
product related documents:
2026 EPA Cert_TVPXL07.7BDA-006 VD230-01, VD250-03, VD275-01.pdf
| Weight | 6450 lbs |
|---|---|
| Dimensions | 156 × 66 × 94 in |
Only logged in customers who have purchased this product may leave a review.





Reviews