Aksa Mobile Generator APD-EPAJ140T4 (140kW)



Aksa Mobile Generator APD-EPAJ140T4 (140kW)
Call for Price
The APD-EPAJ140T4 is a trailer-mounted mobile diesel generator set manufactured by Aksa Power Generation, rated up to 140 kW / 175 kVA standby (130 kW / 162.5 kVA prime) at 60 Hz. Powered by a John Deere 6068HFG05-PVL Tier 4 Final diesel engine paired with a Stamford UCI274G alternator and a DSE 7320 digital control panel, this unit is engineered for demanding commercial, industrial, and mobile prime power applications. Housed in a sound-attenuated steel enclosure mounted on a heavy-duty, DOT-approved dual-axle trailer, it combines rugged reliability and EPA Tier 4 Final emissions compliance with easy transport and straightforward serviceability.
Key Features
- John Deere 6068HFG05-PVL Tier 4 Final diesel engine, 6-cylinder in-line, 160 kWm (215 BHP)
- Stamford UCI274G alternator, Class H insulation, self-excited, 4-pole design
- DSE 7320 digital control panel with MODBUS communication and remote SCADA capability
- Standby rating of 140 kW / 175 kVA and prime rating of 130 kW / 162.5 kVA at 60 Hz
- Multi-voltage capability: 208/120V and 480/277V three-phase, 240/120V single-phase
- Sound-attenuated steel enclosure with lockable, corrosion-resistant access doors
- DOT-approved 10,000 lb heavy-duty dual-axle trailer with spring axles and electric brakes
- 224.5-gallon integral double-wall fuel tank with heavy-duty steel base frame
- EPA Certified Tier 4 Final engine for Mobile/Prime applications
- ISO 9001:2015 certified manufacturing; TS ISO 8528, CE, SZUTEST, and 2000/14/EC certified
APD-EPAJ140T4 product details and specifications:
General Characteristics
- Model Name: APD-EPAJ140T4
- Frequency: 60 Hz
- Fuel Type: Diesel
- Engine Make and Model: John Deere 6068HFG05-PVL (Tier-4)
- Alternator Make and Model: Stamford UCI274G
- Control Panel Model: DSE 7320
Power Ratings (60 Hz)
- 240/120V, 1-Phase, PF 1: Standby 130 kW / 130 kVA (541.66 A); Prime 120 kW / 120 kVA (500 A)
- 208/120V, 3-Phase, PF 0.8: Standby 140 kW / 175 kVA (485.77 A); Prime 130 kW / 162.5 kVA (451.07 A)
- 480/277V, 3-Phase, PF 0.8: Standby 140 kW / 175 kVA (210.5 A); Prime 130 kW / 162.5 kVA (195.48 A)
Engine Specifications
- Engine: John Deere
- Engine Model: 6068HFG05-PVL
- Number of Cylinders: 6, in-line
- Max Power @ Rated RPM: 160 kWm (215 BHP)
- Brake Mean Effective Pressure: 1446 kPa @ prime
- Aspiration & Cooling: Turbo Charged Air to Air After Cooled
- Total Displacement: 415 in³ (6.8 L)
- Bore: 4.2 in (106 mm)
- Stroke: 5.0 in (127 mm)
- Compression Ratio: 17.2:1
- Governor Type: ECU, ISO8528-G3
- Rated RPM: 1800
- Rotation: Anti-clockwise viewed on flywheel
Engine Electrical System
- Charging Alternator: 12V, negative ground
- Alternator Rating: 65 amp
- Starter Motor Power: 3.0 kW
- Starter Motor Rated Voltage: 12 VDC
- Battery Quantity x Rating & CCA: 1 x 80Ah, 700
Fuel System
- Type of Injection: Direct
- Fuel Injection Pump: Denso HP3
- Fuel Prime Pump: Manual
- Max Fuel Flow: 119 kg/hr (262 lb/hr)
- Fuel Filter & Water Separator: Available
Fuel Consumption
- 110% Load (Standby): 9.5 gal/h
- 100% Load (Prime): 8.8 gal/h
- 75% Load (Prime): 7.1 gal/h
- 50% Load (Prime): 5.3 gal/h
Exhaust System
- Exhaust Gas Flow: 18.7 m³/min
- Max Back Pressure: 5.0 kPa
- Max Exhaust Gas Temp in Manifold: 495°C
Cooling System
- Radiator Ambient Temp: TBD
- Coolant Capacity: 43 L (11.359 gal)
- Thermostat Operation Range: 85-97°C
- Combustion Air Flow: 11.4 m³/min
- Engine Coolant Flow: 468 L/min (124 gal/min)
- Cooling Fan Air Flow: 314.73 m³/min
- Max Restriction of Radiator: 0.873 kPa (3.50 in H2O)
- Air Filter: Paper Element
Lubrication System
- Oil Capacity: 32.5 L (8.58 gal)
- Oil Cooler: Water cooled
- Oil Filter: Spin on, replaceable
- Oil Temp (Continuous Operation): 138°C
Alternator Characteristics
- Manufacturer: Stamford
- Model: UCI274G - 60Hz
- Design: 4-pole, drip proof rotating field
- Exciter Type: Self excited
- Stator: 2/3 winding pitch
- Rotor: Single bearing, flexible disc
- Leads: 12
- Insulation: Class H
- Temp Rise @ 40°C Ambient: 125°C Prime
- Max Over-Speed: 2250 rev/min
- Voltage Regulator: AS440
Optional 4-Position VSS (Standard Oversized Alternator kW Rating at 1800rpm/60Hz)
- 480/277V - 3ph - 0.8pf: 184.8 kW
- 240/120V - 3ph / 208/120V - 3ph - 0.8pf: 164 kW
- 240/120V - 1ph - 1pf: 205 kW
Gen-Set Canopy Dimensions
- Length: 153.93 in
- Width: 45.51 in
- Height: 91.14 in
- Dry Weight: 7253 lb
- Fuel Tank Capacity: 224.5 gal
- Genset Sound Level (dBA@23ft): TBD
Base-Frame Enclosure
- Complete gen-set mounted on a heavy duty base frame with an integral double wall fuel tank
- Anti-vibration isolators installed between engine/alternator supports and the base frame
- Enclosure parts designed with module principles, without welding
- Four doors on each side for serviceability, plus a back door for the control system
- Exhaust silencer coated against environmental conditions, internally mounted within enclosure
- Exhaust pipe thermally insulated on engine compartment
- Metal enclosure parts painted with electrostatic polyester powder paint
- Fuel filling cap within the enclosure, reachable through a lockable door
- Emergency stop switch externally mounted on enclosure
- Components installed in sheet steel enclosure
- Phosphate chemical pre-coating of steel provides corrosion-resistant surface
- Polyester composite powder topcoat forms a high-gloss, extremely durable finish
- Lockable hinged panel door provides easy component access
Control Panel
- Control Module: DSE
- Control Module Model: DSE 7320
- Communication Ports: MODBUS
- UL recognized, NFPA110 Level 1 compatible
- LCD text display, key menu navigation and front panel editing
- Off/Manual/Auto mode switch
- Two-wire starting/stopping in Auto mode
- Engine exerciser
- IP65 front panel rating with supplied sealing gasket
- Configurable 8 inputs, 6 analogue inputs, 6 DC outputs with expansion capability
- Real-time clock provides accurate event logging
- Fully configurable via DSE Configuration Suite PC software (license free)
- Remote SCADA monitoring and BMS integration features
Control Unit — Monitored Instruments
- Engine: speed, oil pressure, coolant temperature, run time/battery volts, maintenance due
- Mains: voltage (L-L, L-N), frequency, phase sequence
- Generator: voltage (L-L, L-N), current (L1-L2-L3), frequency, earth current, kW, PF, kVAr, kWh/kVAh/kVArh
- Pre-Alarms: low oil pressure, high/low engine temperature, over/under speed, under/over generator frequency and voltage, ECU warning
- Electrical Trip: earth fault, kW overload, generator over current, negative phase sequence
- Warnings: charge failure, battery under voltage, fail to stop, low fuel level (opt.), kW overload, negative phase sequence, loss of speed signal
- Shutdowns: fail to start, emergency stop, low oil pressure, high engine temperature, low coolant level, over/under speed, under/over generator frequency and voltage, oil pressure sensor open, phase rotation
Standard Specifications
- EPA Certified Tier 4 – Final engine powered generator set for Mobile / Prime applications
- Designed and manufactured in a facility certified to ISO9001:2015 standards
- John Deere heavy duty four-cycle industrial diesel engine for low emission, reliable power, and fast load response
- Non-proprietary control system with total gen-set integrated control, protection, and metering
- Aksa Power Generation provides single-source responsibility for the generator set and accessories
- Generator set and components are prototype tested and production tested
- Stamford industrial generators meet BS EN 60034 and related international standards
- Heavy duty base frame with integral pad vibration isolators eliminates need for under-unit spring isolators
Options
- High oil temperature shut down
- Low fuel level shut down
- Low fuel level alarm
- High fuel level alarm
- Expansion modules: Additional LED module (2548), Expansion relay module (2157), Expansion input module (2130)
Standards
- Electrical Safety / EMC compatibility
- BS EN 60950 Electrical business equipment
- BS EN 61000-6-2 EMC immunity standard
- BS EN 61000-6-4 EMC emission standard
Convenience Panel Accessories
- (2) Two 20A, 120V GFCI receptacles and breakers
- (3) Three 50A, 240V twist lock receptacles and breakers
- 5-15A, 125V inlet receptacles for battery charger and water heater
- Two-wire remote start station
- Generator set voltage adjust rheostat
- (5) 400A rated, stud type quick connect cam-locks
- Oil drain valve & extension
- Convenience panel
- Voltage selector switch – 3 position
- Emergency stop switch
- Battery, battery rack & cables
- Battery charger (Input: 196-264V, Output: 27.6V 5A or 13.8V 5A)
- Main line CB
- Jacket water heater (120 VAC, 1000 W)
- Operations manual
- 1 year / 2000 hours limited warranty
Voltage Selector Switch
- Three positions at 480/277V, 208/120V - 3ph & 240/120 - 1ph
- Product of Salzer or Kraus&Naimer
Standard Features & Accessories
- Trailer w/spare tire and tool box
- Sound Attenuated Steel Enclosure
- Heavy Duty Steel Base-frame
- Exhaust system with DOC+SCR
- Flex Fuel Lines
Trailer
- DOT approved 10,000 lb heavy duty dual axle trailer
- Spring axles with electric brakes
- Breakaway kit with charger
- 5000 lb front jack and rear stabilizer jacks
- 7-pin trailer plug
- Tool box and spare tire
Circuit Breaker
- 500 Amp capacity main line circuit breaker
- Shunt trip controller by generator set control
Optional Accessories
- Upsized alternator
- PMG excitation
- Alternator anti-condensation heater
- 4-position VSS
- Fuel level monitoring on controller & high fuel alarm
- Fuel line check valve
- Oil temperature gauge
- Oil heater
- Battery charger 10 Amp
- Battery heater blanket
- Main line CB (100% rated)
- Remote monitoring and control
- Remote annunciator
Aksa Certificates
- TS ISO 8528
- CE
- SZUTEST
- 2000/14/EC
product specifications:
| Specification | Value |
| Model Name | APD-EPAJ140T4 |
| Frequency (Hz) | 60 |
| Fuel Type | Diesel |
| Engine Make and Model | John Deere 6068HFG05-PVL (Tier-4) |
| Alternator Make and Model | Stamford UCI274G |
| Control Panel Model | DSE 7320 |
| Standby Rating - 240/120V 1-Phase | 130 kW / 130 kVA (541.66 A) |
| Standby Rating - 208/120V 3-Phase | 140 kW / 175 kVA (485.77 A) |
| Standby Rating - 480/277V 3-Phase | 140 kW / 175 kVA (210.5 A) |
| Prime Rating - 240/120V 1-Phase | 120 kW / 120 kVA (500 A) |
| Prime Rating - 208/120V 3-Phase | 130 kW / 162.5 kVA (451.07 A) |
| Prime Rating - 480/277V 3-Phase | 130 kW / 162.5 kVA (195.48 A) |
| Engine | John Deere |
| Engine Model | 6068HFG05-PVL |
| Number of Cylinders | 6, in-line |
| Max Power @ Rated RPM | 160 kWm (215 BHP) |
| Brake Mean Effective Pressure | 1446 kPa @ prime |
| Aspiration & Cooling | Turbo Charged Air to Air After Cooled |
| Total Displacement | 415 in³ (6.8 L) |
| Bore | 4.2 in (106 mm) |
| Stroke | 5.0 in (127 mm) |
| Compression Ratio | 17.2:1 |
| Governor Type | ECU, ISO8528-G3 |
| Rated RPM | 1800 |
| Rotation | Anti-clockwise viewed on flywheel |
| Charging Alternator | 12V, negative ground |
| Alternator Rating | 65 amp |
| Starter Motor Power | 3.0 kW |
| Starter Motor Rated Voltage | 12 VDC |
| Battery Quantity x Rating & CCA | 1 x 80Ah, 700 |
| Type of Injection | Direct |
| Fuel Injection Pump | Denso HP3 |
| Fuel Prime Pump | Manual |
| Max Fuel Flow | 262 lb/hr (119 kg/hr) |
| Fuel Filter & Water Separator | Available |
| 110% Load (Standby) Fuel Consumption | 9.5 gal/h |
| 100% Load (Prime) Fuel Consumption | 8.8 gal/h |
| 75% Load (Prime) Fuel Consumption | 7.1 gal/h |
| 50% Load (Prime) Fuel Consumption | 5.3 gal/h |
| Exhaust Gas Flow | 18.7 m³/min |
| Max Back Pressure | 5.0 kPa |
| Max Exhaust Gas Temp in Manifold | 495°C |
| Radiator Ambient Temp | TBD |
| Coolant Capacity | 11.359 gal (43 L) |
| Thermostat Operation Range | 85-97°C |
| Combustion Air Flow | 11.4 m³/min |
| Engine Coolant Flow | 124 gal/min (468 L/min) |
| Cooling Fan Air Flow | 314.73 m³/min |
| Max Restriction of Radiator | 3.50 in H2O (0.873 kPa) |
| Air Filter | Paper Element |
| Oil Capacity | 8.58 gal (32.5 L) |
| Oil Cooler | Water cooled |
| Oil Filter | Spin on, replaceable |
| Oil Temp (Continuous Operation) | 138°C |
| Alternator Manufacturer | Stamford |
| Alternator Model | UCI274G - 60Hz |
| Alternator Design | 4-Pole, drip proof rotating field |
| Exciter Type | Self Excited |
| Stator | 2/3 winding pitch |
| Rotor | Single bearing, flexible disc |
| Leads | 12 |
| Insulation | Class H |
| Temp Rise @ 40°C Ambient | 125°C Prime |
| Max Over-Speed | 2250 rev/min |
| Voltage Regulator | AS440 |
| Length (in) | 153.93 |
| Width (in) | 45.51 |
| Height (in) | 91.14 |
| Dry Weight (lb) | 7253 |
| Fuel Tank Capacity (gal) | 224.5 |
| Genset Sound Level (dBA@23ft) | TBD |
| Control Module | DSE |
| Control Module Model | DSE 7320 |
| Communication Ports | MODBUS |
| Enclosure Type | Sound Attenuated Steel Enclosure |
| Trailer | DOT approved 10,000 lb heavy duty dual axle trailer |
| Emissions Certification | EPA Tier 4 Final |
| Manufacturing Certification | ISO 9001:2015 |
| Standards Compliance | TS ISO 8528, CE, SZUTEST, 2000/14/EC |
| Warranty | 1 Year / 2000 Hours Limited Warranty |
product related documents:
| Weight | 7253 lbs |
|---|---|
| Dimensions | 153.93 × 45.51 × 91.14 in |
Only logged in customers who have purchased this product may leave a review.